Hawke非铠接管式****格兰(SB474系列)
Hawke****格兰代理商:上海颐品自动化科技有限公司
关键词:Hawke****格兰,Hawke****葛兰,Hawke****填料函,Hawke****密封接头
Hawke非铠****格兰,Hawke铠装****格兰,Hawke****变径,Hawke****呼吸阀堵头
Hawke SB 474 Cable gland(可自行开孔)
Hawke非铠接管式****格兰(SB474系列)
Hawke代理商:上海颐品自动化科技有限公司

Hazardous Area Cable Glands from Hawke
Hawke SB 474 cable glands are suitable for both outdoor and indoor use.
For particular use with:-
a) Cable inner sheaths that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit ‘cold flow’ characteristics.
c) Enclosures for gas group IIC, under 2 litres in volume and containing an ignition source.
d) Enclosures for gas groups IIA or IIB, which are greater than 2 litres in volume and contain an ignition source
Hawke SB 474 cable glands are dual certified Exd and Exe and suitable for installation in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
When used in increased safety applications the Hawke cable gland can be used to terminate braided cables where the braid and the cable outer sheath enter into the electrical enclosure or junction box.
♦ Exdb IIC Gb, Exe IIC Gb, Extb IIIC, Db Non-aromoured Cables ATEX & IECEx Cable Gland.
Hawke SB 474 cable gland is suitable for cable termination and installation in Zone 1 (21), Zone 2 (22) and Division 2 hazardous areas.
HAWKE SB 474 CABLE GLAND TECHNICAL SPECIFICATION
Hazardous Area Cable Gland Classification – Exdb IIC Gb, Exeb IIC Gb, Extb IIIC Db
Certificate No’s – baseefa06ATEX0056X and IECEx BAS 06.0013X
Cable Gland Zone Location – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC
Construction and Test Standards – IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
Ingress Protection – IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X
Deluge Protection – DTS01
Operating Temperature Range -60°C to +80°C
CABLE GLAND SELECTION TABLE FOR HAWKE SB 474
Hawke Size Ref. |
Male Entry Thread Size |
Female Entry Thread Size |
‘G’ Compressed Length |
Hexagon Dimensions |
Metric |
NPT * |
Metric |
NPT # |
Across Flats |
Across Corners |
Standard |
Option |
A |
M20 |
¾” |
½” |
M20 |
– |
63.9 |
30.0 |
32.5 |
B |
M25 |
1″ |
¾” |
M25 |
– |
52.8 |
30.0 |
39.5 |
C |
M32 |
1¼” |
1″ |
M32 |
– |
69.5 |
46.0 |
50.5 |
All dimensions in millimetres (except * where dimensions are in inches).
Metric entry threads are 1.5mm pitch as standard.
# NPT female thread sizes equivalent to those shown in the table for the male thread size are available. Hexagon dimensions as shown may alter.
➡ Cembre cable lugs available to crimp and terminate cable conductors to ensure complete termination of cable.
CABLE GLAND MATERIAL & FINISH
Hawke SB 474 cable glands are manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
PREPARING CABLE & GLAND FOR INSTALLING HAWKE SB 474

CABLE PREPARATION
Pull sufficient length ‘I’ of cable through conduit/cable gland to suit equipment. Screw backnut (1) _disibledevent="word-break:break-all;text-size-adjust:none;margin-top:0px;margin-bottom:0px;font-weight:400;background-color:#ffffff;padding:0px;">